会议专题

Effects of Installation and Winding Distribution on False Detection in Open Type Residual Current Devices

  Installation of residual current devices can effectively prevent electric fire accidents and electric shock hazards.False residual currents (FRCs) have been a fatal issue for the abnormal tripping of residual circuit breakers under heavy current conditions.Analytic method is utilized to illustrate the mechanism of the FRCs.The effects of the installation and the winding distribution are analyzed using the analytic model.The results show that the FRCs are sensitive to the position of supply conductors and the non-uniform winding distribution.Experimental tests are carried out to validate the analytic results with errors less than 5%.

Analytic method false residual currents residual current sensors winding distribution

Wei Chen Guichu Wu Zhichao Hu

Key Laboratory of Low-voltage Apparatus Intellectual Technology of Zhejiang,Wenzhou University, Wenzhou 325027, China

国际会议

The 7th Intrenational Conference on Reliability of Electrical Products and Electrical Contacts(第七届电工产品可靠性与电接触国际会议)

江苏苏州

英文

129-132

2019-11-04(万方平台首次上网日期,不代表论文的发表时间)