会议专题

Capacitor-switching based Method of Network Harmonic Impedance Measurement via TLS-ESPRIT Algorithm

  Capacitor-switching operation can be used to measure network harmonic impedance.Via the transient components of voltage and current after capacitor switching,the harmonic impedance of PCC(Point of Common Coupling)can be calculated.To improve measurement accuracy,the TLS-ESPRIT algorithm is introduced in this paper to filter out noise and fundamental components in voltage and current signals.Via time domain simulations,the advantages of the proposed method in the ability of noise interference resistance and measurement accuracy,are verified compared with the Prony algorithm based method.

power quality harmonic impedance measurement capacitor switching TLS-ESPRIT DFT

Wu Nan Zha Xiaoming

Jiangsu Electric Power Company Research Institute State Grid Nanjing,China School of Electrical Engineering Wuhan University Wuhan,China

国际会议

2017 IEEE 3rd Information Technology and Mechatronics Engineering Conference(ITOEC2017)(2017 IEEE 第3届信息技术与机电一体化工程国际学术会议)

重庆

英文

994-998