会议专题

Icing Flashover Warning Scheme for Composite Insulators Based on Leakage Currents Feature Parameters

  It is urgent to forecast the icing flashover accident of composite insulator as its icing phenomenon has a significant impact on the safe operation of power grid.Although numerous studies have been conducted to predict flashover accident,limited progress has been achieved yet due to the diversity of icing phenomenon and dispersion of icing flashover.In this paper,artificial icing experiments of energized composite insulators with different icing degree and equivalent salt deposit density(ESDD)were performed in the artificial climate chamber.By analyzing the measured leakage current(LC)and flashover voltage,the influence of ESDD and icing degree on LC was investigated.Moreover,three feature parameters of the LC,namely the maximum pulse amplitude(Ih),the total harmonic distortion(THD),and the accumulative charge(Q),which jointly reflect the influence of both ESDD and icing degree,were extracted.All three parameters were converted to corresponding icing flashover voltage via the application of generalized regression neural networks(GRNN)model.Therefore,this paper proposes an elementary flashover warning scheme for iced composite insulators.The relative errors between prediction results and experimental ones are less than 7.78%.

composite insulators icing characteristics GRNN leakage current flashover

SHU Lichun WANG PengHao JIANG Xingliang HU Qin HE Yanzhun

College of Electrical Engineering Chongqing University Chongqing 400044 China

国际会议

第十七届国际结构物大气覆冰会议(IWAIS2017)

重庆

英文

1-4

2017-09-25(万方平台首次上网日期,不代表论文的发表时间)