会议专题

Arc Separating Process Experiment Study in Low Voltage Circuit Breaker

  Weather the arc is separated by the deion plates or not will determine success or failure of interruption for current-limiting circuit breaker.So its important to investigate the separating condition of arc by the splitters.In this study the oscillating circuit is used as supply power.For circuit breaker with 250A frame size, different materials and numbers of splitters are tested in short current interrupting process.Experiment results verified the necessary condition of successful arc separating process.While the arc column voltage is higher than total voltage of separated arc, the arc will be possibly separated.With the increase of splitters number the required current is higher while the other parameters are constant.Larger number of splitters means higher corresponding arc voltage, which may more easily cause back strike.

arc deion plates separating condition

Tiansheng Zhu Hongwu Liu Ruiliang Guan Huilin Chen

State key laboratory of Electrical Insulation and Power Equipment, Xian Jiaotong University, Xian, Changshu Switchgear Mfg.Co., Ltd.(Former Changshu Switchgear Plant) & Jiangsu key laboratory of smar

国际会议

The 6th Intrenational Conference on Reliability of Electrical Products and Electrical Contacts(第六届电工产品可靠性与电接触国际会议)

江苏常熟

英文

176-179

2017-04-18(万方平台首次上网日期,不代表论文的发表时间)