会议专题

Comparison and analysis of protection latency time between intelligent and traditional substations

  In this paper, the protection latency time between traditional and intelligent substations are compared and analyzed. In traditional substation, the analog information such as current and voltage are tranmitted to the protection and control devices via electric cable, while in intelligent substation the introduction of digital protection devices and intelligent substation prolong the protection time, which brings safe threaten to the cutoff of power system fault. The compositions of operation latency time are compared in each link and two major different time latency links are analyzed in details, and the mechanism of time latency is investigated and the effective meausures to reduce the protection latency time are proposed. Finally, the experiment of protection time comparison between two is carried out and the results prove the validity of theoretical analysis.

protection latency time traditoional substation intelligent substation comparison and analysis

Pang Fubin Gao Lei Yang Yi Yuan Yubo

Jiangsu Electric Power Company Research Institute

国际会议

2016中国国际供电会议(CICED2016)

西安

英文

1-5

2016-09-01(万方平台首次上网日期,不代表论文的发表时间)