The Research of Three Phase Four Wire Active Power Filter on Small Independent Micro-grid

  The harmonic had a bad influence on power quality on micro-grid, so it is very necessary to find an effective way to suppress the harmonic. New control method of three phase four wire active power filter (APF) is applied to suppress harmonic in micro-grid in this paper. Compared with traditional single methods, one cycle control method and improved space vector pulse width (SVPWM) method are combined, the new control method omitted the harmonic detection circuit, reduce the switching loss in certain degree and the utilization ratio of the DC side voltage is improved. The model of new control method of three phase four wire APF model and small independent micro-grid model are built. Then simulation analysis on small independent micro-grid harmonic suppression is made. Simulation results show that one cycle controlled three phase four wire APF has a good compensation effect in harmonic suppression on small independent micro-grid.

small independent micro-grid harmonic suppression one cycle control SVPWM three phase four wire active power filter

LIU Yu-hang YANG-jing LI-hao WANG-chao

Logistical Engineering University,Chongqing,401311

国际会议

2016中国国际供电会议(CICED2016)

西安

英文

1-4

2016-09-01(万方平台首次上网日期,不代表论文的发表时间)