Analysis of Incorrect Operation of 220 kV Line Protection Power Converse and Its Improving Measures
This paper analysis a mal-operation event of power converse protection. By deeply analyzing the link between time and mal-operation of power converse protection from theoretical analysis and protective logic, it sums up behaviors of 220 kV line protection tripping behavior under power converse situation,concludes that the reason for mal-operation is power converse protective logic can not adapt to the fault fast removal of the operating conditions. This article presents three measures to these problems. The application results prove the effectiveness of these methods.
power converse pilot protection double-circuit transmission lines differential protection
LUO Bin-bin XIAO Qiong WANG Chang-xiang
Zhongshan Power Supply Bureau,Zhongshan 528400,China Heyuan Power Supply Bureau,Heyuan 517000,China Electric Power Research Institute,China Southern Power Grid,Guangzhou 510623,China
国际会议
西安
英文
1-3
2016-09-01(万方平台首次上网日期,不代表论文的发表时间)