会议专题

The Arcing Fault Based Multi-cycle Incipient Fault Detection for Underground Cable

  This paper proposes a novel method for detecting a multi-cycle incipient fault in an underground cable. The incipient faults are recognized as self-clearing arcing faults and detection method is performed by calculating fault point voltage total harmonic distortion (THD) for all possible distances in the cable. The arc fault is detected when the fault point voltage THD at any assumed fault distance is larger than the threshold. The proposed arcing fault detection method eliminates the effect of fault distance. The proposed incipient fault detection has been verified by PSCAD/EMTDC simulations. Results show that the proposed method is effective and accurate. Lab experiments are also conducted to further validate the proposed detection method.

Arcing fault incipient fault fault detection underground cable

Wenhai Zhang Tuhua Tang Xinglu Yin Guanglong Qu Yang Wang

Maintenance Company of State Grid Sichuan Electric Company; Sichuan University Maintenance Company of State Grid Sichuan Electric Company

国际会议

2016中国国际供电会议(CICED2016)

西安

英文

1-5

2016-09-01(万方平台首次上网日期,不代表论文的发表时间)