Coordinated Voltage Control Using Tiered Weight Coefficients of Optimization Targets
Considering the locality feature of voltage control problems, This paper proposes a coordinated voltage control method with tiered weight coefficients of optimization targets, the optimization problem is formulated and solved based on the model predictive control method. At the initial control time, the correlation degree between buses is obtained based on the dynamic voltage response feature and fuzzy clustering method and the weak buses are identified according to the predicted system trajectory. In the optimization objective function, the higher correlation degree between the controlled buses and the weak buses leads to lager weight coefficients of the corresponding voltage deviation terms. In a fault scenario, the weight coefficients of the optimization targets are tiered-distributed, and the simulation results of the Nordic32 52-bus test system shows that the proposed method remarkably reduces optimization scale under the premise of a global control performance.
tiered weight coefficient coordinated voltage control model predictive control fuzzy clustering
Yan Zhang Yongzhi Su Hengxu Zhang Wen Zhang Xin Wang
State Grid Shandong Electric Power Research Institute,Jinan 250002,China State Grid Shandong Electric Power Company,Jinan 250001,China Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education (Shandong U
国际会议
西安
英文
1-5