Reliability analysis of the protection system in smart substations

  Aiming at implementing the condition-based maintenance of protection systems in smart substation, a new assessment method of the operational level of protection systems is presented. Based on the characteristics of smart substations, a monitoring method reflecting the changes of the protection system function in terms of logical nodes was given first. According to the needs of the condition-based maintenance, reliability indices of the protection system were then selected. Along with these indices, a dynamic Markov reliability assessment model was built to quantitatively calculate the maintenance requirement under given conditions. Finally, a typical 220kV smart substation was utilized to illustrate the application method of the assessment model. The result shows that the method, with certain operability, could provide reference for maintenance decision-making of the protection system in smart substations.

Smart substations protection system reliability Markov model condition-based maintenance

Zhihui Dai Xi Chen Tianyu Zhang

School of Electrical and Electronic Engineering,North China Electric Power University,Baoding 071003 Baoding Power Supply Company,Baoding 071003,China

国际会议

2016中国国际供电会议(CICED2016)

西安

英文

1-6

2016-09-01(万方平台首次上网日期,不代表论文的发表时间)