Fault Line Detection Based on Cross Correlation Coefficient for Distribution Network with DG
This paper proposes a fault line detection method based on cross correlation coefficient for distribution network which has distributed generation (DG). Firstly, Genetic Algorithm (GA) is used to optimize the potential function parameters of bistable system (BS), and bistable system is utilized to extract zero-sequence current in noise background. Then, as for fault line detection criterion, the cross correlation coefficient is calculated between different lines, and the line which has smallest comprehensive correlation coefficient is judged as fault line. At last, simulation experiments prove that the method can detect fault line exactly in different fault environment, including different grounding resistance, fault distance and so on.
Bistable system Distribution network Distributed generation Fault line detection
Jie Gao Qiming Cheng Xiaowei Wang Fengren Tang Yu Zhang Deqing Yu
College of Automation Engineering,Shanghai University of Electric Power,Shanghai 200090,China School of Electrical Engineering and Automation,Henan Polytechnic University,Jiaozuo,454000,China