SSR-Stable Area Analysis of DFIG Based Wind Farms Connected to Series-Compensated Power System
For subsynchronous resonance (SSR) phenomenon indoubly fedinduction generator (DFIG)-basedwindfarmand series compensated transmission network, this paper firstly studies SSR characteristics in all DFIG operation areas, including maximum-power-point-tracking (MPPT), constant rotation speed area and limiting output power area, to obtain SSR-stable area with the finding that SSRcharacteristics varies in different operation areas. With the approach of eigenvalue analysis in all operation areas, this paper further investigates the impact of dominant factorson the range of SSR-stable area. In addition, the impact of the number of DFIGs on the stability of wind farm is studied in particular. In the end suggestions are put forward from both designing and operating aspects for windfarms to reduce the risk of SSR.
DFIG series compensation SSR all operation areas SSR-stable area
Xiaoliang Dong Yazhou Luo Jian Liu Lin Geng Lei Zhang Xu Tian
North China Branch of State Grid Corporation of China,Beijing,China China University of Mining and Technology,Beijing,China
国际会议
西安
英文
1-6
2016-09-01(万方平台首次上网日期,不代表论文的发表时间)