会议专题

Area backup protection based on substations secondary-DC-loss

  A scheme of substation SDL (secondary- DC-loss) protection based on the regional grid information is proposed, which can quickly isolate the fault when the insubstation or outlet-line fault occurs in a substation with SDL. With the substations as the objects, the concept of regional master-slave station protection system and its construction modes are proposed, which realizes the effective detection of the SDL of substation protection system by the aid of the regional process-level communication network and the communication power-supply independent of the protection power-supply, and a complete scheme of SDL protection is further proposed. The results of RTDS test show that, the proposed method and scheme can correctly detect the status of substation SDL and quickly isolate the faults in the SDL area.

Secondary-DC-loss Fault isolation Master-slave station protection system SDL protection

Dai Guangwu Xie Hua Xu Xiaochun Zhao Qingchun

Nanjing Nari Relays Electric Co.,Ltd.,Nanjing,Jiangsu,211102

国际会议

2016中国国际供电会议(CICED2016)

西安

英文

1-4