会议专题

The Improved Thermal-circuit Model for hot-spot temperature calculation of Oil-immersed Power Transformers

  Based on improvement of Swifts black-box thermal-circuit model,this paper establishes a dynamic numerical model suitable for different capacity transformers.According to effect factors of the precision of thermal-circuit model,such as winding losses,oil viscosity changes,heat dissipation conditions,et al,this paper proposed ways to modify the model.The model is proved to be precise by comparing results with factory temperature rise test data.

component power transformer thermal-circuit model transformer capacity hottest-spot

WEI Ben-gang FU Chen-zhao Li Hong-lei LI Ke-jun LIANG Yong-liang

Electric Power Technical Research Institute State Grid Shanghai Municipal Electric Power Company Sha School of Electric Engineering Shandong University Jinan,China