会议专题

A Novel Integrated Disturbance Identification Method for ±800kV UHVDC Transmission Line Protection

  Disturbance on UHVDC transmission line often results in the mal-operation of line protection in practice.In order to ensure the accurate operation of line protection, A novel integrated disturbance identification method for UHVDC transmission line protection is proposed in this paper.The proposed method only need to utilize the voltage information of single pole in one end and realizes the identification of faulty line and lightning disturbance, whose identification principle is based on the different characteristic of voltage.A detailed ±-800kV UHVDC system simulation model, including lightning stroke simulation model, is built and Simulation test results show that the proposed disturbance identification method can distinguish disturbance from fault correctly and rapidly, which provides a strong guarantee for main protection to prevent the mal-operation in the case of disturbance.

Disturbance identification Integrated method Line protection UHVDC system

Fei Kong Baohui Zhang Yanting Wang

School of Electrical Engineering, Xian Jiaotong University, Xian, 710049 China

国际会议

第六届现代电力系统自动化和保护国际会议

南京

英文

432-436

2015-09-21(万方平台首次上网日期,不代表论文的发表时间)