Influence factors and countermeasures of dielectric loss measurement of shunt capacitor of breaker

  Affected by various factors, the result of shunt capacitor of breaker dielectric loss measurement is easily misjudged. In order to avoid misjudgment, this paper analyzes the common three kinds of influence factors: interference signals in the site, Cardon effect and air humidity. Three methods were proposed to reduce these effects, they are frequency conversion and anti-jamming technology, increasing the test voltage and spraying RTV. The results show that these measures can effectively avoid the miscarriage of justice of the test results.

Shunt capacitor of breaker HV dielectric loss Cardon effect serial harmonic RTV

YANG Junting Peng Peng YANG Zhaoguang WEN Dingjun

Gansu Electric Power Research Institute ,Lanzhou, China

国际会议

2015 Joint International Mechanical,Electronic and Information Technology Conference(JIMET 2015)(2015 联合国际机械,电子与信息技术国际会议)

重庆

英文

1031-1034