会议专题

The experimental investigation of temperature rise rate of neighboring tank surface under fire conditions

  In this work, two large oil tank models with 60 cm or 80 cm diameter and 60 cm height are built to study the temperature rise rate of neighboring tank surface with different filling rate.In order to study the temperature rise rate of the neighboring tank surface which is at different location on the neighboring tank surface, both the theory analysis and experiments are considered.It is found that the temperature rise rate of the neighboring tank surface is proportional to the heat radiation.An estimated model has been developed for the temperature rise rate.The data calculated by this model has also been obtained to verifiy compliance with the experimental data, and the results show that it fits well.

Oil tank fire Heat radiation Temperature rise rate Filling rate

Changfa Tao Xuedong Chen Zhichao Fan Ruowen Zong

Hefei General Machinery Research Institute,No.888,West Changliang Road,Hefei 230031,China State Key Lab.of Fire Science,University of Science and Technology of China,No.96JinZhai Road,Hefei

国际会议

2015 International Symposium on Structural Integrity(2015年国际结构完整性学术会议)

沈阳

英文

91-96

2015-05-16(万方平台首次上网日期,不代表论文的发表时间)