Simulation on Phase Angle Difference between Voltage of Metering Port and Bus of 220kV CVT
In order to study how parameters of CVT affect the phase angle difference between Voltage of Metering Port and Bus Voltage, an EMTP model with actual parameters of a 220kV CVT was established to simulate how some parameters affect the phase angle difference, such as value of voltage-dividing capacitors and its dielectric loss, ratio of transformer, coil turns of compensation reactor and the load.The result is shown as followed: (1) The increasing dielectric loss of high voltage capacitor will make phase angle difference decrease significantly, while the increasing dielectric loss of medium voltage capacitor will make phase angle difference increase significantly;(2) Decrease of the ratio of transformer will make phase angle difference increase a little;(3) Increase of capacity and power factor of load will make phase angle difference decrease.These results are available to CVT testing online.
capacitor voltage transformer (CVT) phase angle difference parameters
Bingbing Cai Chun Liu Danjiang Wang Zhiming Cui Qian Wang Zhenbiao Li
State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan 430074, China
国际会议
温州
英文
280-284