Research on Fault Location Algorithm for Double Transmission Line on the Same Tower Based On the Conductor’s Relation of Electromagnetic Coupling
The Six-Sequence Fault Components was used for fault location Algorithm of double lines on the same tower commonly.But the Algorithm is greatly influenced by the parameters symmetry of transmission line,and particularly,the algorithm will bring bigger error when the conductor transposition is not perfectly.The paper analyzes the error of the fault location Algorithm based on the models of complete transposition and no-complete transposition.According to the results of the above analysis,the paper raises a fault location method by using the electromagnetic coupling relationship between double lines.The PSCAD simulation test indicates that the new method has higher accuracy.
double transmission line on the same tower fault location no-complete transposition
Kunyi Chen Qin Ai Shaowu Li Dongshan Geng Yongchao Yang
Hubei University for Nationality,Enshi HuBei,445000,China
国际会议
长沙
英文
2150-2155
2014-05-31(万方平台首次上网日期,不代表论文的发表时间)