Analysis of the characteristics of solar-powered absorption chiller running with compression refrigerator
A joint operation system of solar-powered absorption chiller and compression refrigerator was established in this paper,which solar conditioning was used for undertaking air conditioning peak load.First,solar fraction of the operation mode was defined,and then operation working condition in summer was simulated with Trnsys for long time.Research results showed that the solar fraction can be 6.4%,12.2%,17.35%,22.11%,when the absorption chiller undertook 10%,20%,30%,40%peak load.Finally,the energy conservation and economy were analyzed.Reasonable load ratio absorption chiller undertook under different collector price and efficiency,were obtained and reference data for promoting the use of joint operation was provided.
Solar-powered absorption Solar fraction Peak load Load ratio