会议专题

Load Frequency Control for Power Systems with Wind Turbines

  In this paper,a two-degree-freedom(TDF)internal model control(IMC)method is applied to the load frequency control(LFC)of multi-area power systems with of wind turbines.TDF-IMC needs only to tune two parameters and can achieve good disturbance rejection performance.For implementation,IMC controllers are approximated with PID controllers.A frequency response dynamic model including simplified wind turbine is used in the design and simulation,and the physical constraints such as generation rate constraint(GRC)and speed governor dead band are considered.Simulation results show that the proposed method can damp the frequency and tie-line exchange power deviation quickly,and is robust to parameter variations.Furthermore,the participation of wind turbines in LFC can enhance the total system performance.

load frequency control (LFC) internal model control (IMC) wind turbine robustness

CHEN Wen TAN Wen

School of Control & Computer Engineering,North China Electric Power University,Beijing 102206

国际会议

The 33th Chinese Control Conference第33届中国控制会议

南京

英文

4277-4282

2014-07-28(万方平台首次上网日期,不代表论文的发表时间)