Research on Harmonic Current Detection Method Background of Microgrid

  Due to the type of power in the microgrid are numerous, intermittent and randomness, and is accompanied by a large number of inverters , so the power quality problems such as harmonics are produced. For this resort, this paper presents a new power quality detection method, this method used the Chain Mixed Morphological Filter (CMMF) instead of the Low-Pass Filter (LPF) in the conventional ip—iq detection method based on the instantaneous reactive power theory, it maked many Mixed Morphological Filters gettd serially concatenated, and rational choosed the shape and length of the structural elements of each Mixed Morphological Filter, to achieve the best detection.Simulation results show that, this method can be fast and accurate detection of harmonic signals.

Microgrid Morphological filter Harmonic current Detection method

Li Shengqing Zeng Huanyue Li Weizhou Xu Wenxiang Lin Hongzhi

Hunan University of Technology,Zhuzhou Hunan,412008,China Zhuzhou Electric Power Bureau,Zhuzhou Hunan,412000,China

国际会议

2013 IEEE 11th International Conference on Electronic Measurement & Instruments(第十一届IEEE国际电子测量与仪器学术会议)

哈尔滨

英文

233-236

2013-08-16(万方平台首次上网日期,不代表论文的发表时间)