会议专题

The corrosion behavior of galvanized steel in alkaline soil

  The grounding grid of some substation shows severely corrosion,which affects the safe running of power grid.Galvanized steel is widely used in grounding grid.However,the galvanized steel is easy to corrosion in alkaline soil.In this paper,the corrosion behavior of galvanized steel was studied through accelerated corrosion test of burying specimens in laboratory soils and the corrosion rate was measured by electrochemical test.The corrosion products and corrosion appearance were analyzed by means of SEM,and XRD.The results show that pitting corrosion and localized corrosion were observed on the surface of the galvanized steel,the corrosion products were rough and loose,indicating no protection,the corrosion products of galvanized steel were ZnO,FeO(OH),FeC13,Zn3O(SO4)2,and ZnSO3·2.50H2O.Electrochemical test show that the corrosion rate of galvanized steel in the later corrosion stage is higher than in the initial corrosion stage.

galvanized steel grounding grid soil corrosion electrochemical accelerated corrosion

YAN Feng-jie LI Xin-geng WANG Xue-gang

Shandong Electric Power Research Institute,Jinan 250002,china

国际会议

2013 International Conference on Process Equipment,Mechatronics Engineering and Material Science(2013过程装备,机电工程与材料科学国际学术会议)

武汉

英文

416-420

2013-06-15(万方平台首次上网日期,不代表论文的发表时间)