会议专题

Analysis of optimum U-tube diameter in ground source heat pump

  In order to reduce the pump energy consumption in GSHP,pipe diameter is increased to solve the problem.When flux of pump is constant,by choosing pipes of different diameters for numerical calculation and simulation,the pump energy consumption and the heat transfer of ground heat exchanger are both analyzed.It could be concluded that an appropriate increase of pipe diameter could reduce pump energy consumption and enhance heat transfer.However,when the pipe diameter is too large,the hot short circuit of ground heat exchanger would be serious,thus,increase of pipe diameter should be based on the hot short circuit between branch pipes.It is given in the paper that the suggest pipe diameter would exist during 30 mm to 40 mm.The analysis would reduce energy consumption of pump,improve a guarantee for the selection of pipe diameter and the design of GSHP with great guide and economic benefits.

ground source heat pump pipe diameter energy consumption hot short circuit

H.L.Zhang Y.J.Yu

Energy and Mechanical Engineering Academy, Nanjing Normal University, Nanjing, China

国际会议

2012 International Conference on Frontiers of Energy and Environmental Engineering(2012年第二届能源与环境工程前沿国际会议(ICFEEE2012))

香港

英文

354-357

2012-12-01(万方平台首次上网日期,不代表论文的发表时间)