Analysis of 220kV Transformer Tripping Accident Caused by Neutral Point Gap Breakdown

  Through the neutral point of the main transformer is breakdown gap under the lightning over-voltage,and the main transformer is tripped by the zero-sequence protection,the discharge dispersion of gap is large is indicated; When 220kV neutral point is ungrounded,the protection must be sharing after arrester parallel gap is proposed.The two-phase or three-phase wave is the main reason of the protection device action are pointed by discussing the wave process in the transformer; The most simple and effective way is placing special transparent insulating over the gap is proposed.

effective grounding over voltage protection gap arrester wave process