DETERMINATION OF EJECTOR AREA RATIO AND SYSTEM PERFORMANCE OF A COMBINED EJECTOR-VAPOR REFRIGERATION CYCLE

  In this paper,the key ejector geometry parameters for an air-cooled ejector sub-cycle in a combined ejector-vapor refrigeration cycle (EVCC) using R134a are designed by 1D analysis.Through enlarging the designed area ratios by connecting the replaceable nozzles with a main body,optimum area ratios under air-conditioning working conditions are studied experimentally.The optimum area ratios are from 3.09 to 4.16 that are lower than those mentioned in other studies.With a fixed ejector area ratio of 3.69,experiments on the EVCC performance show that: 1) The combined cycles performance is most sensitive to the ejector evaporating temperature with given operating conditions; 2) On average COP improvement of 16.3% over the vapor compression sub-cycle was obtained when ejector generating temperature is at 78℃ and ejector evaporating temperature and compressor frequency and EEV opening percentage are at 13-19℃,30-50Hz and 40-80%,respectively; 3) Real operating conditions of the combined cycle such as ejector evaporating temperature,compressor frequency and EEV opening percentage should be chose with regard to both the EVCCs COPs and COP improvements.