会议专题

Comparison of Different Fault Detection Statistics Detectability in PCA

  Detectability of the sensor fault detection system is the basic criteria for selecting of different fault detection statistics.PVR and CVR in MPCA are compared with T2H.The complementary among them is analyzed qualitatively.Results of power plant data simulation show that PVR and CVR in MPCA can improve sensor fault detection,but T2H is still better for some sensors.Combination of PVR,C VR and T2H can improve sensor fault detectability of PCA-based fault detection system.

process monitoring fault detection Principal component analysis

Tian Qiu Xiaojing Bai

Key Laboratory of Measurement and Control for Industry Process North China Electric Power University Beijing, China

国际会议

2012 2nd International Conference on Computer Application and System Modeling(2012第二届计算机应用与系统建模国际会议)(ICCASM-2012)

沈阳

英文

462-465

2012-07-27(万方平台首次上网日期,不代表论文的发表时间)