Study on Anti-corrosion Performance of 20A & 316SS in Circulating Cooling Water with Different Concentration Ratio
The corrosion behaviour on 20A carbon steel and 316SS in cooling water were studied through weight-loss measurements in different concentration ratio condition.The results obtained from this study showed that inhibitors played obviously effective role for 20A material,while inhibitors had no any positive effect to 316SS material; and concentration ratio 3~7 range was suitable for protecting both 20A and 316SS materials in power plant.
Concentration Ratio Circulating Cooling Water Weight-loss Measurement
Dingping Zhong Kang Juan Fan Gao Heng Zheng
Guangdong Clean Environmental Protection Technology Co.,Ltd, 8 Yunhe North Street, Xianlie Central R School of Chemistry & Boilogical Engineering, Changsha University of Science & Technology,960.Wanjia
国际会议
太原
英文
753-756