Application of compressed air foam system in extinguishing oil tank fire and middle layer effect
Firstly,compressed air foam system (CAFS) was briefly introduced.The difference of foams produced from low expansion foam extinguishing system and CAFS were compared according to macro parameters and micro parameters.Secondly,thickness of tank shell,thickness of tank bottom,intensity of water supply and intensity of foam solution supply were determined according to codes.Then oil tank for model test was designed with the help of Auto Computer Aided Design (Auto CAD) and completed using Q345R steel plates.Finally,small-scale model tests were carried out to examine extinguishing effect of CAFS onto oil tank fire.Three conclusions were as follows.The oil tank designed according to codes could endure the flame radiation.CAFS could be applied in extinguishing oil tank fire.The torch-like flame when the fuel level was high and ball-like flame when the fuel level was lower could be explained using theory of middle layer effect.
oil tank fire small-scale model test compressed air foam system Auto Computer Aided Design middle layer effect
FU Xuecheng BAO Zhiming CHEN Tao Xia Jianjun ZHANG Xianzhong ZHANG Jin HU Yingnian
Fire Extinguishing Agent Research Division.Tianjin Fire Research Institute of MPS,Nankai District,Tianjin 300381,China
国际会议
2012 International Symposium on Safety Science and Technology (2012安全科学与技术国际会议)
南京
英文
669-673
2012-10-23(万方平台首次上网日期,不代表论文的发表时间)