The Using of Insulated Fiber Bragg Grating Temperature Sensor in 35kV Switch cabinet
In long-period running of switch cabinet,the temperature of contact points will be rose by the big contact resistance,poor contact and longtime overloading.Overheat can cause oxidation of contact points and the increasing of contact resistance,and then the contact may be generated the spark and arc discharge.That is a bad circle.So the temperature of contact points can affect the reliability of switch cabinet.For detecting the temperature of contacts and the switch cabinets environment in Yanjin transformer substation,we design an Insulated FBG temperature sensor.The surveys of upper reaches indicate that the temperature of moving contact A gets the maximum 32.98℃ Aug.20,2011,the temperature of stationary contact A gets the minimum 5.75℃,and the change temperature between contacts and environment gets the maximum 2.82℃.According to relevant state regulations,the contacts temperature of 70 ℃ and temperatures changes of 35 ℃ in the case of environments temperature below 40℃ are Alarm threshold value of switch cabinet.
Switch cabinet FBG Temperature Sensor Insulated Fiber Brag Grating Temperature Sensor
Yanrfeng Chen Chuan Li Yunshui Xu Qinghua Yan Shaoguan Zhang Yan Chen Xiaoping Xu Jiangchun Xu Yingna Li
Faculty of Information Engineering and Automation,Kunming University of Science and Technology,Kunmi Zhaotong power supply bureau,Zhaotong,657000,China Electric Power Research Institute,Yunnan Provincial Electric Power Test & Research Institute(Group)C
国际会议
西安
英文
1055-1060
2012-06-12(万方平台首次上网日期,不代表论文的发表时间)