会议专题

The Influences of Main Ingredients of the Reclaimed Water on Calcium Carbonate Scale in Recycling Cooling System

  The main risk of reclaimed water reused in industry is to control fouling.The main ingredients in reclaimed water form the chemical scale which is one of the main components of the fouling in the recycling cooling system.The main chemical scale of reclaimed water is carbonate scale (calcite).In this paper,by using the actual reclaimed water which reused as make-up water in Beijing Thermal Power Plant to simulate the 4 times concentrate ratio recycling water to study the influence of main ingredients of reclaimed water such as pH,soluble silica,the most content of anions and cations on carbonate scale.The experimental results show that pH,soluble silica,calcium ion and alkalinity have greater influence on scale inhibition,but magnesium ion,chloride ion and sulfate ion have smaller influence on scale inhibition.

the reclaimed water water ingredients calcium carbonate scale scale inhibition

Guanhua Yue Limin Shang Liping Wang Lili Feng

Key Laboratory of Urban Stormwater System and Water Environment Beijing University of Civil Engineering and Architecture, Ministry of Education, Beijing, 100044,China

国际会议

the 2011 International Conference on Biotechnology, Chemical and Materials Engineering (2011生物,化学与材料工程国际会议(CBCME 2011))

昆明

英文

1554-1557

2011-12-28(万方平台首次上网日期,不代表论文的发表时间)