会议专题

Design of Grid Connected Parallel Inverters with Interleaved Phase Shift by Using CAN Bus

  A grid-connected parallel inverter with interleaved phase shift is proposed in this paper.The synchronous are generated by the master module to achieve interleaving phase shift PWM for the parallel inverters connected to grid-tied system that make the inverter to output current to the power line and share the load.TI TMS320F2812 DSP is used for system feedback control with voltage and current by using A/D converters to generate the output current close to sine wave.The expected output current values are determined by the master module and transmitted via CAN (Control area network) between inverter modules.The grid-tied system uses zero-voltage-detection circuit to synchronize the inverter currents with grid voltage.For each switching period,PWM voltage of two inverters are interleaved to reduce the total output current ripple so that the switching frequency can be reduced and the power system EMI problem can be alleviated as well.The experiment results are provided to verify the performance of the proposed system to reduce output current harmonic distortion.

Grid Connected Inverter Parallel Inverter Interleaved Phase Shift

Jyh-Wei Chen Huan-Fu Lin

Department of Vehicle Engineering,National Formosa University,Taiwan Mechanical & Electro-Mechanical Engineering,National Formosa University,Taiwan

国际会议

the 2012 International Conference on Manufacturing Engineering and Automation (2012年制造工程与自动化国际会议(ICMEA2012))

广州

英文

1579-1584

2012-11-16(万方平台首次上网日期,不代表论文的发表时间)