Wall Socket Fire Analysis
Fire scene investigation on fire caused by the wall socket,extracted the copper bead and aluminum wire material evidence,observe and analysis,include the macro analysis and metallographic analysis,and then confirmed the reason.Through the identification of the extractedfire material evidence,macro features are all electric heated,the metallographic analysis to determine the nature of the melted marks respectively for primary short circuit melted marks and over load melted marks and short circuit spatter melted mark.These three kinds of trace is in line when the electrical fault occurred formed,and a primary short circuit melted marks provides the most direct strong scientific basis for the cognizance of the fire,and determined the fires is caused by the faulted wall socket.
Aluminum Wire Fire Short Circuited Solidification Mark Organization
Lian Tie Wang Qing Shan Meng
Shenyang fire research institute,Shenyang 110034;Key laboratory of fire scene investigation and evidence identification,Ministry of Public Security,PR China,Shenyang 110034
国际会议
广州
英文
2414-2417
2012-11-16(万方平台首次上网日期,不代表论文的发表时间)