会议专题

Theoretical Analysis on Pollution Flashover Voltage Prediction Based on Leakage Current of Porcelain Insulator in Service

  In this Paper,leakage current obtained by laboratory was derived to calculate the pollution flashover voltage of porcelain insulators.On this basis,this Paper analyzed the basic theory of prediction of pollution flashover based on leakage current monitored in service.At the same time,the calculation results and the test results of pollution flashover voltage were compared The results showed that the difference of flashover voltage between calculation results and test results was less than 5%.It is proved that the calculation method for evaluating the flashover risk by monitoring the leakage current proposed in this Paper was effective.

porcelain insulator DC leak age current pollution flashover voltage

Lei Song Fuzeng Zhang Xidong Liang Yifan Liao

Department of Electrical Engineermg,Tsinghua University,Beijing,China Electric Power Research Institute,CSG,Guangzhou,China

国际会议

2013 International Conference on Information, Business and Education Technology (2013信息、商业与教育技术国际会议(ICIBET 2013))

北京

英文

1306-1309

2013-03-14(万方平台首次上网日期,不代表论文的发表时间)