Fault Diagnosis Method for Transformer Bushing Based on RS Theory and Influence Factors Analysis
Based on the test results of dielectric loss factor (tan8) of transformer bushings in an artificial climate chamber, in this paper a Decision Table to analyzed the influence of tan5 is built which based on the Rough Set (RS) theory, and the effect of environment factors and voltage on the tan8 of capacitive equipment was analyzed by the Rough Set theory, and the results shows that the influence of temperature and humidity is much more than the voltage, which can be ignored. However, the old bushing is more influenced by the humidity factor compared to the new one. So, the fault of capacitive equipment can be diagnosed by RS theory and influence factors analysis.
Tano Influence Factors Rough Set Diagnosis
Hongliang Liu Yongqiang Wang
North China Electric Power University, Baoding, Hebei Province, China Hebei Electrical Power Researc North China Electric Power University, Baoding, Hebei Province, China
国际会议
哈尔滨
英文
322-326
2012-05-19(万方平台首次上网日期,不代表论文的发表时间)