会议专题

Fault Diagnosis Method for Transformer Bushing Based on RS Theory and Influence Factors Analysis

Based on the test results of dielectric loss factor (tan8) of transformer bushings in an artificial climate chamber, in this paper a Decision Table to analyzed the influence of tan5 is built which based on the Rough Set (RS) theory, and the effect of environment factors and voltage on the tan8 of capacitive equipment was analyzed by the Rough Set theory, and the results shows that the influence of temperature and humidity is much more than the voltage, which can be ignored. However, the old bushing is more influenced by the humidity factor compared to the new one. So, the fault of capacitive equipment can be diagnosed by RS theory and influence factors analysis.

Tano Influence Factors Rough Set Diagnosis

Hongliang Liu Yongqiang Wang

North China Electric Power University, Baoding, Hebei Province, China Hebei Electrical Power Researc North China Electric Power University, Baoding, Hebei Province, China

国际会议

2012 International Conference on Future Communication and Computer Technology(2012未来通信与计算机技术国际会议ICFCCT 2012)

哈尔滨

英文

322-326

2012-05-19(万方平台首次上网日期,不代表论文的发表时间)