Method of Parallel Active Power Filter Compensation on 3-phase 3-wire Nonlinear Unbalanced Load System
The parallel active power filter has been accepted by users because of its installing and removing without disturbing other users and so its detecting and controlling algorithms have been studied with large efforts .A method about direction of active power flow (DAPF ) was raised in present paper under condition of the 3-phase asymmetrical voltage and 3-wire nonlinear unbalanced load. Its means that detected currents on the point of common coupling can be put into two parts according the active power flow direction ,one of which is called positive direction current and another is called negative direction current .then decompose the asymmetrical voltage and positive directional current with Symmetrical Component Method. We can obtain the reference current components with clear physical meaning for the paralleled active power filter .The method shows there are several harmful power components could not be eliminated with parallel active power filter.
Parallel Active Power Filter Direction of Active Power Follow Symmetrical Component Method Current physical Component theory Asymmetrical 3-phase Voltage
Zou wen-xue Liu sheng-hui
School of Electric and Electronic Engineering,Harbin University of Science and Technology, Harbin. 1 School of Software Engineering,Harbin University of Science and Technology, Harbin. 150040