A Study of Earthing System Using Reinforcing Bars in House Foundation Using by Real Scale Experimental Model
An earthing system that uses a house foundation was designed.The earthing resistance of the minimum experimental mat foundation model (about 1.3m2 in area) on outdoor was less than 90 Ω at over 100 kHz on a lightning surge equivalent frequency and stayed between 30 Ω and 50 Ω over time.When the earthing system was constructed in the house, it was suggested that it could be applied as a less-than 100 Ω earth because the impedance resulted capacitive from the frequency characteristics.The earthing system with surge protection devices suggested having the overvoltage control effect.
component Earth Lightning Protection Surge Protection Devices (SPD) Foundation of a House
Masatoshi Ohshima Fumiya Nakazato Nobuhiro Watanabe Hirotaka Shimizu Noriyuki Mita Hisashi Yamasaki
Research & Development DivisionKawamura Electric Inc.Seto-city,Aichi,Japan Department of Electrical System EngineeringPolytechnic UniversitySagamihara,Japan Department of Electrical EngineeringPolytechnic UniversitySagamihara,Japan Department of Architectural System EngineeringPolytechnic UniversitySagamihara,Japan Department of Architectural System Engineering Polytechnic University Sagamihara,Japan