Influence of Grounding Conditions on SE of Shielded Room in LEMP Environment

In order to analyze the influence of grounding conditions on the shielding effectiveness (SE) of shielded room, numerical simulation is done by applying parallel Finite-Difference Time-Domain (FDTD) method on the coupling problems between shielded room and lightning electromagnetic pulse (LEMP) environments.Inner coupled electromagnetic (EM) fields are calculated when the shielded room is with different grounding locations and schemes.The results indicate: (1) the farther the distance between the grounding location and the aperture, the better the SE of shielded room, the nearer the worse.(2) The SE is related to the different grounding schemes (single-point grounding and multipoint grounding).For a better SE to LEMP, shielded room should use single-point grounding.

Finite-Difference Time-Domain (FDTD) method shielded room lightning electromagnetic pulse (LEMP)environments grounding conditions

Jian-bao Wang Bi-hua Zhou Bo Yang Jian-ming Guo

National Key Laboratory on Electromagnetic Environmental Effects and Electro-optical EngineeringPLA National Key Laboratory on Electromagnetic Environmental Effects and Electro-optical Engineering PLA

国际会议

第七届亚太防雷国际会议

成都

英文

1-4