Optimum Location of Measurement Electrode when Testing the Grounding Resistance of an L-shape Building Base
The characteristics of potential distribution in grounding resistance measurement of an L-shape building foundation using straight-line-three-probes method are analyzed in this paper by numerical simulation when the measurement locations are different while the length of loop electrode lead is the same.The zero potential regions corresponding to allowable engineering measurement error range are also given.Simulated results show that the measured performance is relatively better than other measurement locations when the exterior convex corner of L-shape building base is selected.The studied results can serve as a guideline of important significance to test grounding resistance for large-scale irregular grounding system such as L-shape building base in practical measurement.
straight-line-three-probes method grounding resistance measurement large-scale irregular grounding system measurement position three-dimensional finite difference method
Wenchun Liao Jiaqing Chen Yingqiang Wang Xiangyu Liu
National Key Laboratory onElectromagneticEnvironmental Effects andElectro-optical EngineeringPLA Uni National Key Laboratory onElectromagneticEnvironmental Effects andElectro-optical EngineeringPLA Uni National Key Laboratory on Electromagnetic Environmental Effects and Electro-optical Engineering PLA
国际会议
成都
英文
1-5
2011-11-01(万方平台首次上网日期,不代表论文的发表时间)