Verification of model reliability in a double-grate biomass boiler
A double-grate biomass direct-fired boiler is designed and modified with connected reciprocating grate and oscillation grate based on a 48t/h boiler current operation status. Ribbon and smoke are used in the cold experiments which are based on the reformed hot conditions to verify the model reliability. To have well comparison with the model result, the air ratio and inlet angle of the second air are changed and used to obtain the characteristics of the flow field of the actual grate boiler furnace. And it is the best working condition that the ratio of the air distribution primary air: second air: ignition air is 4: 4: 2, frontwall second air: backwall second air is 5: 5, the inlet angle of the frontwall second air rises 10°, the inlet angle of the backwall second air is in equilibrium position.
model reliability cold condition biomass boiler reliability verification
Ying Zhao Tiecheng Wang Ning Wang Qiuluan Chen Zhihua Ge Qiang Lu Changqing Dong
National Engineering Laboratory for Biomass Power Generation Equipment, School of Renewable Engineering, North China Electric Power University, Beijing, 102206, China
国际会议
合肥
英文
406-409
2011-09-23(万方平台首次上网日期,不代表论文的发表时间)