会议专题

A New Method to Reduce the Interconnection Transients of Induction Generators

This paper presents a novel method to reduce the inrush currents produced by interconnecting induction generators. The method is based on the sequential energization of the contactors and a grounding resistor connected at the neutral point of a wyeconnected stator. Analytical developments are presented, which permit to determine the optimum value of the neutral resistor directly. Theoretical and simulation analysis show that the proposed method can be almost as effective as the traditional three series resistor method. The proposed method requires only one resistor and one bypass contactor and is therefore more cost-effective than the traditional methods.

Distributed generation induction generator inrush current interconnection transients

Ke Zhu Xiaohui Lu Bo Zhang

Shandong University Jinan China

国际会议

2011 3nd International Conference on Mechanical and Electronics Engineering(2011年第三届机械与电子工程国际会议 ICMEE2011)

合肥

英文

524-528