会议专题

Research on an Improved Control Strategy for Harmonics Restraint of DFIG System

An improved control strategy for harmonics restraint of doubly fed wind power system is studied in this paper. Considered low order current harmonics (5th, 7th and so on) caused by the distortion or unbalanced grid voltage conditions and the variations of generator itself parameters, an improved control strategy is proposed. In this control strategy, a proportional integral (PI) regulator paralleled with a harmonic resonant (R) controller in the synchronous reference frame is proposed for restraining the stator current harmonics. The control strategy presented in this paper has not effect on the control of fundamental current, and need not the harmonic separation filter and the sequence decomposition in multi reference frames. To verify the effectiveness of this control strategy, simulation model of DFIG system is developed in Matlab/Simulink, and experiments are implemented on the doubly fed experiment platform. The results of both simulations and experiments show that the control strategy proposed in this paper could restrain harmonic currents effectively and it is easy to implement digital control.

Wind power Doubly fed induction generators Harmonic restraint Resonant controller

Meng Yanfeng Dong Zhiran Hu Shuju Xu Honghua

Institute of Electrical Engineering, CAS, Beijing, China Key Laboratory of wind power, CAS, Beijing, Binjing Corona Science & Technology Co., Ltd, Beijing, China

国际会议

2011 3nd International Conference on Mechanical and Electronics Engineering(2011年第三届机械与电子工程国际会议 ICMEE2011)

合肥

英文

1338-1343

2011-09-23(万方平台首次上网日期,不代表论文的发表时间)