会议专题

Test for Error of Current Transformer Based on Low-voltage Extrapolation Method

The extrapolation method for the error test of the current transformer is to tests the current transformer on-site as a voltage transformer with the same error, which firstly test the error, admittance and other parameters of the trans-former at 200%to 1000% rated voltage or current, then test the admittance at l%to 120% rated voltage or current, and finally achieves the error through the calculation. Its application will bring a great influence on the test of the current transformer on-site.

current transformer voltage transformer error extrapolation method

GUO Mingliang

College of Electrical and Information Engineering Heilongjiang Institute of Science and Technology Harbin, China

国际会议

2012 International Conference on Measurement,Information and Control(2012测量、信息与控制国际会议 ICMIC2012)

哈尔滨

英文

630-633

2012-05-18(万方平台首次上网日期,不代表论文的发表时间)