会议专题

New Inverter Fault Current Limiting Method by Considering Microgrid Control Strategy

In this paper we present an approach for fault cunent limiting(FCL)in inverters of a Microgrid.For this purpose,which is based on the control system employed in Microgrid,we select the proper FCL technique.In this research it is represented that FCL inverter current with limited magnitude of id and iq that are used in PQ control dont have a good behavior in V-F controlled DG.Current limiting by decreasing the output voltage of DG is performed by the value of inverter reduction of the voltage that is selected by paying attention to the maximum current that is allowed through inverter,this value is two times of the rated current of inverter.

Fault Current Limiting (FCL) Microgrid Voltage Frequency Control (V-F) Voltage Source Inverter (VSI)

Kaveh Najafzadeh Hosein Heydari

Iran University of Science & Technology,Tehran,Iran

国际会议

2012 2nd International Conference on Advanced Material Research(2012 第二届先进材料研究国际会议 ICAMR2012)

成都

英文

1647-1653

2012-01-07(万方平台首次上网日期,不代表论文的发表时间)