VOLTAGE SAG SOURCE LOCATION: A NEW METHOD BASED ON CURRENT INFORMATION
In this paper a new method is presented for voltage sag source location based on directional overcurrent (DOC) relay information.In this method the current (during sag and presag) is the only variable which is measured by relay/power quality (PQ) monitor.Then relative location of voltage sag source is determined using the variation of the magnitude of measured current positive-sequence component and the sign of its phase-angle jump.The performance of the proposed method is compared with distance relay (DR) and phase change in sequence current (PCSC) methods by using PSCSD/EMTDC and MATLAB on a large scale actual regional network including transmission and subtransmission levels.The results show the good performance of the new method and its unique applicability in cases where only currents are recorded.
Power quality (PQ) voltage sag (dip) source location phase-angle jump
YOUNES MOHAMMADI ATIEH DELAVARI MOHAMMAD H.MORADI
Bu Ali Sina University Hamadan,Iran Bu Ali Sina University Hamden,Iran
国际会议
成都
英文
2377-2382
2011-11-25(万方平台首次上网日期,不代表论文的发表时间)