会议专题

A New Algorithm of Phase to Ground Fault Location for Electric Power Feeder

As to power supply reliability and smart grid, it is very significant to locate feeder fault quickly and accurately for distribution network.A new method is proposed, which aims at analyzing timefrequency traveling-wave signal caused by ground fault.By decomposing the aerial mode component and zero mode component of fault current based on EMD, the method can get multi-stage stable intrinsic mode function (IMF).The first IMF contains high frequency components, which can reflect the mutation of signal. Hilbert-Huang transformation is done for the first IMF to get the instantaneous frequency of signal.And then the moment of traveling wave arrival can be detected by observing the instantaneous frequency in the figure of IMF time-frequency.The fault distance is computed based on the difference of wave arrival time between aerial mode component and zero mode component.Simulation shows that this method can accurately determine the distance of fault and doesnt be influenced by the random fault condition, such as fault transition resistance and the moment of fault.

Distribution network Hilbert-Huang Transformation feeder fault location phase to ground fault

Yan-Song Wang Yong-Chang Guan Xue-Min Liu

College of Information and Control Engineering,China University of Petroleum,Qingdao,China Dongying Power Supply Company,Shandong Province,Dongying,China

国际会议

2011 IEEE International Conference on Smart Grid and Clean Energy Technologies(2011 IEEE智能电网与清洁能源技术国际会议 ICSGCE2011)

成都

英文

426-429

2011-09-27(万方平台首次上网日期,不代表论文的发表时间)