Refrigerant Distribution in a Parallel Flow Heat Exchanger Having Vertical Headers
Refrigerant R-410a flow distribution is experimentally studied in a test section simulating a parallel flow heat exchanger having vertical headers with two pass configuration. Tubes are heated to yield a test section outlet superheat of 5 ℃ with inlet quality of 0.3. Mass flux is varied from 50 kg/m2 s to 70 kg/m2 s. Results show that, significant liquid flows through bottom channels, and less liquid is supplied to top channels. It’s shown that with proper selection of inlet and outlet location, thermal degradation can be minimized within several percent.
Flow distribution Heat exchanger Header Heated tube
Howon Byun Naehyun Kim Jaeho Lee
Department of mechanical Engineering University of Incheon 406-772 Republic of Korea