会议专题

Forecast of Out-of-Step Section in Complicated Power System

Accurately forecasting out-of-step section is very important to the correct action of out-of-step splitting devices. By analyzing the phase-angle difference change feature of branch in different location of network in time of one machineinfinite system losing stability, it is pointed out that out-of-step section only can occur in the middle part of lines between groups or vicinity. For complicated multi-machines system, based on network parameter, by means of coupling thinking, vulnerability location which is inherent in network is identified, then the phase-angle difference change feature of branch in different location is combined in vulnerability location, out-ofstep section in complicated multi-machines system network is forecasted. Simulation and analysis on New England 10 machines system testifies the validation of the proposed method.

Branch phase-angle difference coupling cut-set weight coefficient vulnerability location out-of-step section

MENG Xiangxia Qiao Zhanjun

North China Institute of Science and Technology, Beijing 101601,China

国际会议

2012 International Conference on Intelligent System Design and Engineering Applications(2012年智能系统设计与工程应用国际会议 ISDEA 2012)

三亚

英文

266-269