COMPARSION OF BUILING CODES AND INSULATION IN CHINA AND ICELAND
Heat load calculation for a sample building with and without insulation using Chinese and Icelandic building codes was carried out in this paper. The results shows that the calculated heat load is similar by the two different building codes for the un-insulated building. This confirms that there is agreement between the calculation methods. Heat load decreases by 36.4% when insulation is added to the building envelope. If the thermal insulation property is improved to satisfy the Icelandic standard, which was valid at the time of construction for the sample building, the heat load decreases to 54.8%, which indicates that improving thermal insulation and insulation properties are effective ways to reduce energy consumption.
Lei Haiyah Pall Valdimarsson
Tianjin University Geothermal Research and Training Cente92 Weijin Road, Nankai District Tianjin 300 University of Iceland Hjardarhagi 2 IS-107 Reykjavik an Enex ehf. Skulagata 19 IS-101 Reykjavik ICEL