Control Strategy Study on Drum Water Level of Supercharged Boiler based on Radiation Energy Signal
The deficiencies of drum water level control system and unstable combustion of supercharged boiler could result some serious accident such as water level fluctuating greatly, pipes in furnace overheating and bursting, boiler loss water. In order to solve the problems, flame detect system was used to get flame images of boilers furnace, and radiation energy signal was introduced into drum water level control system to add one auxiliary control loop of combustion side. The new control strategy was established and simulation model was set up. The simulation results show that the new control system could adjust feed water within 20s, and eliminated the disturbance of water level within 60s by way of monitoring radiation energy signal, the fluctuating range was also decreased significantly.
Supercharged boiler Radiation energy signal Control strategy of water level
Guoyi ZHOU Wensheng HE Huaichun ZHOU
School of Naval Architecture and Power, Naval University of Engineering, Wuhan, 430033, China State School of Naval Architecture and Power, Naval University of Engineering, Wuhan, 430033, China State Key Laboratory of Coal Combustion, Huazhong University of Science and Technology,Wuhan, 430074
国际会议
2011 International Conference on Mechatronics and Materials Processing(2011年机电一体化与材料加工国际会议 ICMMP)
广州
英文
1872-1875
2011-11-18(万方平台首次上网日期,不代表论文的发表时间)